MSL World class environment friendly products for a diverse range of applications
 
  Power Quality Equipment
   Harmonic Filters
 STATCOM
 DVR's
  Power Savers
   SAVELEC
 PCS
 VARONE
 FAQ's
  Power Factor Correction
   APFC
 FPFCC
 FAQ's
  Active Controllers
   AMFC Panel
  Renewable Energy
 
 
Dynaspede’s Power Systems Division offers a range of products and services in Power Electronics and Energy Management.
The group’s intense efforts in the Power Sector Products are geared towards Energy Efficiency, Reactive Compensation, Power Quality, Renewable Energy, Power Engineering and Domestic Products.
 Harmonics
Modern electrical equipment demands Power Quality, which imposes stringent demands on voltage stability and power quality. The power network has to be free from harmonics and other electrical disturbances.
Multiple Frequency Currents and Voltages existing in the Power System, which are integral multiples of fundamental 50 Hz waveform, are called Harmonics, or “dirty power”. Odd positive and negative sequence harmonic currents, are generated by three-phase full wave, non-linear loads, which are connected to a three-phase, three or four-wire distribution system. Odd positive, negative and zero sequence harmonic currents are
generated by single-phase, full-wave non-linear loads which are connected phase to neutral in a three phase, four wire distribution system. Harmonic Currents produce Harmonic Voltage distortion also depending on system impedance. The major contributors of Dirty power (Harmonics) are:
Variable speed drives
Power rectifiers
UPS, SMPS of computers and the like, LAN/ Servers, printers
Photo copiers, Facsimiles,
Electronic ballasts
Virtually all-low power electronic devices
Saturated Cored Transformers, inductors and chokes.
Zero sequence harmonic phase currents are in-phase unlike positive and negative sequence harmonic currents displaced by 120°. Arithmetic combination of these Zero sequence currents happens at Distribution transformer’s terminal and return to their source via the neutral conductor. In certain cases, the resulting neutral current can exceed twice the phase current. This can be detrimental to the distribution system and the transformer, apart from increasing the system losses appreciably.
Effects of Harmonics:
Increased losses, e.g. machines will operate at increased temperature and can be overheated
Resonance problems between the inductive and capacitive parts of the power network
Malfunctioning of control systems since electronic meters, relays, etc. are matched to the fundamental frequency
Overloading of capacitors, leading to malfunctioning and premature aging
Interference with telecommunications and computers
Disturbances in ripple control systems
High currents in neutral conductors.
Solution to Harmonic Problems
Solutions to Harmonic Problems are available as custom-made products from the Dynaspede Power Systems’ product range. A Passive Harmonic Filter called `ESCOFILTER’ is available for a wide range of applications. Both Tuned and De-tuned Filters are available .Zero sequence, inductive filters are also designed, manufactured and supplied, according to customer requirements.
By installing Harmonic Suppression Systems, you can:
Filter Harmonics in the system
Achieve higher power factor, improved voltage stability and network losses, recovering up to 30% of wasted system electrical capacity
Avoid resonance problems and amplification of electrical disturbances
Lengthen the life of your equipment as the “clean” network imposes much less strain on it
Lower the maintenance cost and lower the cost for replacing worn-out equipment
Eliminate expensive electrical system downtime
Escofilter Features:
Single or multistage as required
Manual switching for single stage and Automatic Switching for multistage applications
Single-tuned, Multi-tuned and High-pass Filter Banks available
Bank Voltages from 415 Volts to 33 Kv
Reactive power ratings from 10KVAR to 1000 KVAR (L.V)
Up to 10 MVAR in Medium Voltages
Fully coordinated protection package engineered to meet customer requirements and performance specifications
Rugged capacitors
Film & Foil Capacitors for the Medium Voltages and Heavy duty capacitors for the L.V systems.(up to 690 volts).
Product Specifications

Our Filter Bank incorporating heavy duty capacitors has low loss Polypropylene Film, discharge Resistors and is leak-free. The design can withstand high inrush currents, hence trouble-free.

ESCOFILTER has 1/3 phase iron-core dry type reactors, Copper windings with Class F or Class H insulation. It is designed for 50° C rise over the ambient temperature. These are shunt Filters normally used for shifting natural/resonant frequency of electrical system under harmonic influence and improves power factor for fundamental frequency and reduce distortion levels based on individual system characteristic and filter design.
Type of Filters:

Classification of Harmonic Filter is based on its Filtering capability by its tuning class, which in turn is based on the Absorption duty cycle of Harmonic Filters as well as savings. Dynaspede offers:

  • Tuned Filter
  • De-tuned Filter
  • Zero Sequence Filters

Specifications and Design of ESCOFILTER and its components are based on the following variables.

  • System Short Circuit Level
  • Existence of other Harmonic Filter and Shunt Capacitor Banks
  • Rating and type of Non-linear load to be filtered
  • Plan for future system expansion
  • Ambient voltage distortion.
  • Harmonic Spectrum, THD levels and TDD level.
There are several satisfactorily working ESCOFILTERS in India and other countries, for different applications.
 
STATCOM – Static Reactive Power Compensator

Electrical loads generate and absorb reactive power in the process of their work. Since the transmitted Power and load varies considerably from time to time in the course of an hour, the reactive power balance in a grid varies as well. The result can be unacceptable voltage amplitude variations, a voltage depression, or even a voltage collapse. A rapidly operating Static Reactive Compensator (SRC) can continuously provide the reactive power required to control dynamic voltage swings under various system conditions and thereby improve power system transmission and distribution performance. A Dynamic response system such as SRC will provide the necessary amplitude and phase angle support for the voltage waveform. Installing an SRC at one or more suitable points in the network can increase Power transfer capability and reduce losses while maintaining a smooth voltage profile under different network conditions. In addition, an SRC can mitigate active power oscillations through voltage amplitude modulation.

Dynamic Reactive Compensation

The power flow on utility grids consists of both active and reactive power. The difference is due to the fact that the wave of alternating current always leads (capacitive load) or lags (inductive load) the voltage wave. Reactive power (measured in volts-amperes reactive, or VAr) is the product of voltage and out of phase component of alternating current.

Utilities and industries pay close attention to reactive power because it determines how the voltage declines or 'sags' on an electric network. To stabilize voltage conditions, the generated reactive power has to be compensated. To an electric power consumer, optimisation of an existing power system increases productivity, decreases utility charges, and improves equipment reliability.

 
DVRs – Dynamic Voltage Restorer

With the advent of efficient, fast and compact power electronic devices, quality Power solutions have become much easier and feasible. Dynaspede has developed new applications to improve power quality in the electrical power supply, by providing Dynamic Responsive Correction Systems for the Sags and Swells. These new products facilitate increased reliability and better control of the power flow in electrical transmission systems. This directly influences profitability and boosts the bottom-line for both electrical suppliers and industrial end users.

Industrial electricity consumers constantly fear the negative effects of disturbances in the power supply that can be detrimental for their processes. A short sag (dip) in the supply voltage can stop an entire production line in highly sensitive industries, from computer chip manufacturing to textiles, with losses running to millions.

These concerns can now be put to rest with Dynaspede SRCs and DVRs, to be used separately or in conjunction by the Utility and the Consumer. The DVR provides the required buffering to ride through voltage transients (dips, sags and swells) without affecting the production line. Connected in series between grid and protected load, it compensates transients caused by faults in the transmission or distribution system, securing safe power supply to the load. The DVR stabilizes the voltage directly at the facility level, which normally is Medium Voltage in the distribution system.

The DVR can be sized to any voltage and load requirement, but is best suited for medium voltage (MV) or low voltage (LV) applications. The DVR stabilizes the voltage directly at the facility level, which normally is MV in the distribution system.

 
Power Conditioner Model SAVELEC
A Power Conditioner saving Energy for domestic and small commercial establishments, which regulates voltage and improves power factor
SAVELEC is a power conditioning equipment for electrical utility systems beyond the distribution board. It is essentially a Power Quality Equipment suitable for Small Commercial Establishments, , Small Industries, Homes and apartments. The equipment is connected after the meter and is provided with an input MCB for protection.

SAVELEC is a three-in-one concept with the following features:

  • Conditioning the voltage wave form by smoothening the crest factor
  • Regulation Of voltage
  • Improvement of Power Factor
Principle of Operation

SAVELEC Power Saver is a Wave Form Profile Corrector and a dynamic Line Voltage Conditioner, along with a dynamic near unity power factor corrector. SAVELEC is an intelligent unit incorporating a micro-controller to continually optimise and adjust the Power transfer to the load as per its requirements. A low loss variable reactance and a variable capacitor provide the correct matching impedance for the load circuit there by improving the efficiency in the transfer of Power. Thus, optimal input power is achieved by the optimization of Voltage, current, and power factor depending upon the load, resulting in substantial power savings.

SAVELEC saves 18 to 20% power in normal lighting, fan and other small single-phase loads, subject to the system characteristics. SAVELEC Units are available in Single-phase version or in Three-phase version depending upon the type of load.

Technical Features
An intelligent micro-controller with a built-in software program adjusts the system impedances by switching in appropriate inductance and capacitance into the circuit using high break and make relays to facilitate input current reduction.
Protection to the input and isolation for the equipment are provided using adequately rated MCBs on the line.
SAVELEC ensures reduction in the voltage distortion of waveform and provide reactive current support. This reactance in the equipment also provides surge impedance which will reduce the effect of spikes and transients.
SAVELEC obviates any requirement of voltage stabilizers.
A changeover switch is provided for the bypass of the equipment in the event of any failure of components of SAVELEC.
Options of solid-state relays and manual operations are available.
 
Power Conditioner Saver Model PCS-45

Power Conditioners Savers (PCS) are waveform correction and power factor improvement devices done on phase-wise loads using the latest RISC micro-controller.

A low loss continually variable reactance and adjustable phase-wise capacitance provides optimum impedance for the circuit for maximum power transfer.

Over 25% savings in electricity consumption are achievable in lighting systems (Fluorescent and Sodium Vapour Lamps), and substantial savings in mixed loads (A/C, Fans, Coolers, Appliances) with the use of PCS.

Technical Features
PCS is a powerful Micro-controller & RISC processor with inbuilt programme which intelligently matches system voltages and currents for optimum power transfer.
Intelligent switching operation, fast response, high break relays
Power on indication and current transformer polarity reversal indication
Phase-wise reactive compensation dynamically provided for current reduction
Special Features:
Indication of ‘ON’ ‘OFF’ capacitive elements depending on loading and usage of VI sin Ø
Benefits:
Lighting efficiency improvement, saving over 20%
Voltage wave form profile correction
Phase-wise reactive compensation dynamically provided for current reduction
Series inductive impedances smoothen voltage waveform
Shunt capacitive elements give localized dynamic VAr compensation
Advantages of using power conditioners:
Reduces:
Unbalance current by adjusting phase reactive requirement
Neutral current
System current & (I2R) losses
Reactance’s in system:
Provides power quality reducing input side voltage distortion from entering end use device
Smoothens voltage waveform providing ideal crest factors and saving considerable energy
Street light energy saving above 25% up to 35%
Operational specifications:
Voltage level: 400 volts - 450 volts, III phase, 50 hz AC system
Operating power factors: 0.6 - 0.99 lag
Suitable for lighting loads & mixed loads
Savings in Motors depends on Specific Customer Loads
Optional specifications:
Time based ON/OFF, energy, monitoring, remote control
Data logging & profiling of energy & demand control options available
 
VARONE Power Savers
The intelligent Power Saver that saves 7–15% in electricity every month
Range:
For small 3 phase connections - 1.5 kva for loads of 7 - 8 HP
For medium sized loads - 15 kva for loads up to 50/55 HP
Functions vert efficiently under 3 phase balanced & unbalanced conditions
Technology:
Dynaspede has manufactured Varone using state-of-the art technology with RISC Processor and built-in high-end real time software, which empowers the product with a host of features and facilities.

Technical Features:
Auto switch ON & OFF VAR compensation unit
Individual phase sensing and correction
Individual phase voltage & current data acquisition (independent of each other)
Improvement of power quality by improving load side voltages and half cycle sag correction
Adjustable threshold VAR values for load under varying load patterns
Minimises systems losses
Reduces neutral current and incoming power
High running capacity switches for capacitance Cut-in & Cut-off
Completely enclosed and industrial grade powder coated casing for hazard-free operation and maintenance
Control fuses for the control module

Benefits:
Power factor improvement in the range of at least 0.90 - 0.95 for industries with 40 HP and above, leading to saving PF surcharge by Electricity boards
Auto switch OFF - Unit automatically shuts off the capacitance from the lines thereby eliminating the chances of failure in electrical appliances, motors etc., and additional losses in electricity
LED Indicators:
To indicate switch ‘ON’
To indicate fault
 
FAQ On Power Saving Products
What is the Principle of Operation Of SAVELEC / PCS-45?

The principle of operation of the equipment is based on two fundamental aspects of maximum power transfer. The Maximum power transfer theorem says that when the impedance of the system is equal to the load impedance, maximum power will be transferred.

They are ideal crest factor of the voltage waveform and ideal power factor of the current waveform. These are properties associated with the power supply system and depend on the distribution as well as the end use equipment characteristics.

The equipment optimizes the voltage waveform by inserting the necessary inductances, and reduces the phase angle of the current wave form by injecting the appropriate capacitances. This ensures that there are no deficiencies in the power transfer to the electrical appliances, and thereby reduces the losses. This results in saving of Power.

How is SAVELEC Different From PCS?

SAVELEC is relatively low current application device, which has one multi-tapped inductance for each phase and different capacitor stages for the same phase. Depending upon the load, the power factor of the current wave form changes and accordingly the capacitance needs to be added to meet the reactive power requirement of the load. The micro controller in the equipment senses the active and reactive power component of the load and accordingly adjusts the input voltage and the current phase angle by switching in the respective inductance stage and capacitance stage.

In the case of PCS, Inductance is varied by the use of a motorized Variac, which will ensure smooth variation in the inductance of the equipment. Other than this, this equipment also has a wide dynamic range of operation from 180 volts to 260 volts between the phase and the neutral. PCS has heavy materials and is relatively much heavier than the equivalent size of SAVELEC. Both the ranges are not conflicting in the capacities, but complementary to each other.

The SAVELEC range is available up to 27 Kva in three-phase model and the PCS range starts from 30 kva up to 60 kva. In selective cases, PCS of 25 kva or even less are supplied to meet certain specifications. SAVELEC is suggested where finer corrections are not required, and savings of 15-20% are possible with coarse corrections.

PCS is suggested where finer corrections are required and sensitive loads are present.

What are the functions of SAVELEC?

SAVELEC is a power conditioner with the following operational features:

  • It is a wave form smoothening Device
  • It acts as voltage regulator with in a small band.(Stabilizers can be removed)
  • It acts as a Power Factor Corrector (Capacitors can be removed to the extent dynamic compensation provided)
  • It works as a detuned filter for the third harmonic currents, so that harmonic resonance is avoided
What are the Functions of PCS?
PCS also provides all the above benefits with faster response and with finer corrections. Facilities, which use PCS, can do away with Stabilizers and can do away with fixed capacitances. The PCS series will also act as a series surge suppressor for transients. This will also reduce the reactive unbalance in the distribution system and thereby reduce the neutral currents.
How do we determine the equipment capacity?

The equipment capacity is determined by the load that is connected to the output of the equipment, its nature and type. The three-phase currents on full load is measured along with the voltages of individual phase with respect to neutral, and power factor. If the power factor is found to be better than 0.8, then a multiplying factor of 1.2 is considered on the line current (Balanced currents in all three phases are considered—if there is heavy imbalance, it has to be physically balanced. If the power factor is below 0.8 and is above 0.65, a factor equal to 1.32 times the line current is considered for calculating the capacity.

Once the current level are thus calculated, the equipment capacity is determined by dividing the calculated current by a factor of 1.35, which gives the KVA rating of the equipment.

In case the voltages in the system are below 220volts, no major savings are possible except correction of the PF and reduction in I2 R. losses.

The existence of lumped input capacitances is not detrimental to the application of SAVELEC or PCS, in the feeder or sub-distribution boards in buildings or factories.

What happens when SAVELEC/ PCS trips?
When the SAVELEC/ PCS trips or changes over to the Direct Mode (upon overloading), the savings do not occur. The bypassing of equipment in this mode not only adds power quality issue to the load, but also drives more current in the load circuit. The equipment can be brought to the Save mode once the fault (under which the equipment tripped) is rectified.
When do the Equipment Trip?
The equipment is provided with input protection against Overload and output Short circuit. In the event of any of the above, the equipment MCB/MCCB trips. At this juncture, the user can manually bypass the equipment by changing over the bypass switch to the Direct Mode. In the event of overload, the equipment sensor circuit initiates an automatic bypass of the equipment, and when the status quo resumes, the equipment will be automatically switched over to the Save mode.
What is the Life of the equipment?
The equipment is designed to last over 10 years.
What is the Warrantee period?
The warranty of the equipment is for One Year from the date of Supply.
Can the Consumer get the colour of his choice for the equipment?
For large volume customised orders, we can assure the customers the choice of colour. A small incremental lead-time shall be provided for the delivery.
Where is the equipment installed After / Before Meter?
SAVELEC and the PCS are DSM products, which are basically end–use energy efficient products. They are connected after the Utility Energy Meter and after the main switch of the customer's loads. The total distribution of loads can be sub-divided into different DBs and the equipment can be sized according to the current levels at the DB’s. Closer to the load and optimum the switching currents, higher the benefits to the customer in terms of loss reduction and power quality improvement.
What are the safety precautions to be taken?
  1. Input side overload /short circuit protection.
  2. Earthing terminals for earthing the body of the equipment.
  3. Overload Bypass and automatic restoration.
Is it safe to keep the equipment within the reach of Children?
The equipment shall be installed in safe places out of reach of children or people who are not conscious about the significance of electric safety and dangers of electric shock. The equipment contains several electrical points which are live and dangerous to touch once the front door is opened. It is advised that only experienced and proficient electricians or technicians handle the equipment.
How can the savings be verified?
  1. By comparing the instantaneous value of Power and current drawn in the circuit with the equipment in Save mode and Direct mode for the same load by changing the knob of the changeover switch with a duration of 10 – 30 minutes.
  2. By installing an energy meter (optional) in series, the energy consumption in the save mode and in the Direct mode can be checked by the selection of the changeover switch for fixed duration (same duration) and with fixed load (same load).
What are the precautions needed if more load is to be added?
If more load is to be added, kindly get in touch with our service engineers along with existing load data and capacity of the equipment. They will study the system and either add the load to the equipment, (if provision of expansion in the load is available), or bye-pass the additional load.
Does the Dynaspede Power equipment need any Govt. approval for installation?
The equipment being marketed are tested at reputed laboratories for the features and facilities offered. Since this equipment is a demand side product, meant for improvement of the quality of power supply, no electricity company approvals are necessary.
Are there any other benefits if we use the equipment?
The equipment being a power conditioner, the localized VAr compensation provides voltage support, improves the operating performance of the end-use equipment and increases the life of the devices connected to the equipment. The equipment reduces the reactive unbalances and provides for current reduction using dynamic phase-wise VAr compensation.
What are the tax benefits available?
Both SAVELEC and PCS are Energy saving equipment and hence are qualified for 80% depreciation in the first year of purchase/ Installation as per the relevant Income tax rules. This could mean a lot for corporations/ Firms/ Individuals to offset their tax liabilities.
In case the savings do not match expectations, what is to be done?
In case of large mismatch in savings according to user perception, you may inform our service engineers who will come and demonstrate the correct use of equipment and the conditions to operate. There can be variations in load, input supply of power and incorrect usage. Our Engineers will educate to the clients on all aspects of usage for optimum benefit.
What is the service back up for the product?

We have service centres in almost all the metros and mini metros, with service engineers located at each of these centers, who are available on call, during the Warranty period and later. Normal rectification time in Metros and minimetros is 48 hours. In the absence of a full-fledged service centre near any other city/ town, you may approach our authorized dealer/ stockist for the correction of the equipment.

In places where our service centre is not available, the rectification duration shall be between 72 hours to 96 hours, depending upon the area, distance, and transport availability.
Can the equipment be used for Three-phase motors?
The SAVELEC and PCS are not suitable for three-phase motor loads since the correction of the equipment does not support flux control required by the motor, which operates on Electromagnetic Induction principle. However, starter losses can be reduced by providing the Power Conditioners.
What types of loads can SAVELEC and PCS be used for?
Normal types of loads such as fluorescent lights, fans, small power loads, other single phase loads, small heaters, etc.
What are the typical Savings in the Power Envisaged?
For the conditions of voltages, PF and current levels mentioned in the specifications of the product, a power saving of 15-20% is achievable. In the case of Street Light loads, where the criticality of luminous intensity at off peak hours is not critical, the savings can be above 30%.
What are the operating conditions of the equipment?

The operating conditions of the equipment are

  • Supply input voltages of 415 volts 3-phase, 230 volts single-phase
  • Typical loads as mentioned above—lighting and mixed loads
  • Operating load factor of above 70% on the capacity of equipment
  • No overload conditions
  • Temperature of 30°C and up to 40°C
Automatic Power Factor Correction System (APFC)

The Intelligent Automatic Power Factor Correction Panel with 3Ø sensing and correction is the ideal solution for larger loads and accurate correction to maintain high Power Factor, reduce KVA requirement and save Power.

Special Features

Sturdy Powder coated panel for long life
MCCB Incomer, each stage provided with MCB and Contactor and efficient design to limit inrush currents
Heavy Duty Capacitors with long life and minimum losses
Easy and efficient installation for good energy savings
Available from 25 Kvar at 440V onwards to 500 kvar at 440 volts from 3 stage up to 12 stage
Advantages of using ESCOVAR Panels

Reactive Power requirement as supplied by the panel will release substantial KVA capacity from the transformer.

Loading on Transformers is reduced, which in turn reduces the thermal stress, enhancing in the working life of transformers.

Separate VAR compensation eliminates the magnetizing current passing through the transformer to the loads, thus reducing the losses in the transformer (kwh) for savings.

Automatic compensation helps in maintaining near unity Power Factor at the Secondary side of the transformer thereby facilitating full utilization of Active Power Flow (KW) and at the same time without over compensating the system.
Electricity Utility Networks

The total electricity being distributed by Utilities in India is around 1,20,000 MW. So far most utilities depend on their own VAR compensation systems at the substation points to reduce their T & D losses. Now, given the impending power famine, it is increasingly important to reduce the transformer losses and improve the system voltage by suitable compensations throughout the electrical system.

A transformer is one of the most essential equipment for transmission and distribution of electricity. According to estimates, every megawatt of power capacity needs around 6MVA of power transformer. Distribution losses in India account for almost 18-20% of the total transmission and distribution (T&D) losses of around 26%. The no-load losses of a typical 100KVA distribution transformer is around 460 watts, and this can reduced by 75% by providing suitable VAR compensation using Automatically Switched Shunt Capacitor Banks at the secondary side.

Circuit compensation is useful in augmenting the reactive power requirement of the distribution system. Here, load centre compensation (at the 440volts/415 volts secondary) can be to the extent of 50% of the reactive power requirement. This ensures that during peak load times, the reactive power to the load is fully met and the voltage support required to prevent an undervoltage condition can be built up.

In the next stage, 30% of the reactive power can be provided at the Medium voltage level, again for voltage support and reactive power graded support.

Electricity boards and companies can substantially reduce loss due to undervoltage and earn revenue by employing a KVARH supply through ESCOVAR at the Transformer secondary, and can ask for Independent Reactive power suppliers.
 
Fixed Power Factor Corrector Capacitor (FPFCC)

Capacitors are Reactive power generators, by virtue of the supply of leading currents to the system. The most Economical way of providing reactive compensation for fixed loads, is to connect the required KVAR of capacitor across the motor terminals.

We are supplying Capacitor banks of ratings from 5kvar 3- phase to 500kvar 3-phase in different denominations. These capacitors are heavy-duty capacitors with long life and suitable for motor duty applications. These can also be connected to the mixed loads, provided the loads are of constant nature.
 
FAQ on Power Factor

Power Factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. Power factor is a measure of how effectively the current is being converted into useful work output. It is a good indicator of the effect of the load current on the efficiency of the supply system.

Power Factor It is a measure of the effect of the phase lag and harmonics of the input current on the main efficiency.

The power factor (P.F.) is defined by:

Power factor, cosq = P/S = Active power / Total apparent power

For the above power factor is inclusive of the harmonics

P.F. can be expressed as:

P.F. = Cosq1. Cosj1

Where
q1-  Phase lag between current & voltage caused by inductive nature of the load
j1-  Phase lag between current & voltage caused by harmonics in the supply which is produced by non-linear loads such as UPS, etc.

Theoretical Meaning of Power Factor
Can Power Factor Be Corrected?

Power factor can be improved by using the following equipment:

  1. Static capacitors
  2. Synchronous condensers
  3. Phase advancers

Static capacitors and synchronous condensers draw leading current and partly or completely reduce the lagging current in the load circuit, thus improving the power factor.

Phase advancer is an AC exciter which matches the stator winding current with the supply voltage. They are used in motor control applications.

Typically, the most economical solution used to improve power factor is a capacitor bank.
Standard applications without static capacitors

Typical Electrical load connected to the supply without connecting capacitors

Power factor in the range of 0.7 to 0.8
Reactive power also supplied by the power source only
Power factor improvement using static capacitors  
Power factor Vs Current (Load)
Advantages of Power Factor Correction
Advantages
  1. Reduces line losses
  2. Reduces line current
  3. Improves line voltage
  4. Curtails voltage drop
Indirect Benefits
  1. Due to reduction in current, heating power dissipation loss will be minimal for the same conductor
  2. Power loss will be minimal
  3. Frees up system capacity
Power factor improvement for Variable loads

Intelligent and Automatic power factor correction Panels with Automatic sensing and Correction systems are provided to enable Accurate correction on larger intermittent inductive loads.

If capacitors are added into the circuit for the total connected load and manually operated in plants equipped with very large intermittent inductive loads, such as large motors, compressors, etc., then the capacitors produce excess leading current when the load is switched off, leading to inaccurate power factor improvement.
Product Architecture
 
Digital Automatic Mains Failure Control (AMFC) Panel

Dynaspede’s automatic mains failure control panel is a microprocessor digital unit offering all basic functions needed for the automatic control of a Generator set-up (Genset)

The unit is housed in a sheet metal enclosure Length 250 mm, Width 420 mm and Height 600 mm. The panel has a door with a glass window for visibility of the indications and display parameters.

The panel is provided with four eyebolts at the top for lifting and powder coated with Siemens Grey colour shade.

In automatic mode, the unit monitors 3 phases of the mains supply and controls the automatic starting and stopping. When the engine is running, the unit monitors the fault conditions and shuts down the engine automatically in the occurrence of an alarm. The alarms are identified by a group of LEDs displaying only the first occurrence one.

The occurrence of the any of the faults mentioned below stops the engine immediately.
  • Over speed
  • Under speed
  • Low generator voltage
  • High engine temperature
  • Low lube oil pressure
The AMF panel provides factory-adjusted timers. These settings can be adjusted as per the user’s need on specifying the requirements in advance. The unit uses high current two part connectors for easy replacement.
Features
Automatic engine starting and stopping
Automatic mains failure monitoring
Automatic shutdown on fault condition
Mains 3 phase voltage inputs
Genset phase voltage input
Survives cranking dropouts
Mains phase voltage limit checking
Genset phase voltage limit checking
Delayed over speed and under speed alarm
Lamp test
Selectable lube oil pressure and oil level switch
Plug-in connection system for easy replacement and serviceability
Modes of Operation
OFF: Mains contactor is be energized if AC mains are present
AUTOMATIC: The unit monitors 3 phases of the mains supply and starts the genset and controls the changeover of mains and genset contactors if mains failure on any phase is detected.
RELAY OUTPUTS
EB Mains Contactor
Generator mains contactor
Alarm relay
Engine fuel solenoid stoppage
Auxiliary relay
Ignition power
LED ANNUNCIATION
EB mains
Generator mains
Alarm relay
Copyright © 2010 MSL .com.
Home About Us Contact Us